Example: Smart Socket

Build turn-on and turn-off commands for a smart socket end to end — payload, encoder, verification, and running them from the States tab.

This walkthrough builds two commands on one device and verifies that they worked. It uses a mains-powered smart socket that reports whether its relay is on or off, but the same sequence applies to any actuator: a valve, a luminaire, a heater.

Follow it in order — each section produces something the next one needs.

Before you start

  • The socket is registered and transmitting. Class C for LoRaWAN, or an MQTT device.

  • You can see its readings on the Metrics tab (Mapping for MQTT).

1. Find out how the device reports its state

Open the device and go to the Metrics tab. Look through the connector keys table for the field that carries the relay state, and note two things: the field name, and the value it is showing right now.

For this socket:

Connector key
Current value

socket_status

off

That value is what a verification check will compare against later, so write it down exactly as it appears — off, not OFF or false.

If the field is not mapped to a metric yet, map it now: the command editor selects sensors by their metric name, so an unmapped field cannot be used to verify anything. See Payload Decoding and Connector Keys.

In this example socket_status is mapped to a metric named Socket status.

2. Create the Turn ON command

Open Commands & States → Commands and click Add new command.

The command editor with the identity, routing and payload sections of a device command

1. Identity

  • Command nameTurn ON

2. Routing

  • For LoRaWAN: set the fPort the device expects, and turn Confirmed downlink on.

  • For MQTT: enter the topic the socket subscribes to for commands.

3. Payload

This command takes no parameters — it always sends the same thing — so add none, and define the payload the encoder should build. The socket expects three bytes: channel 0x08, type 0x70, and the state, 0x01 for on.

Use Try Encoder to check the result before saving. It shows the encoded output in hex and base64 with its size in bytes, so you can confirm the payload is 08 70 01 before the command ever reaches the device.

4. Verification

Choose Wait for next uplink — the socket reports its state in every routine message, so there is no need to poll it.

Under Expected sensor states, click Add State:

  • MetricSocket status

  • Expected valueon

Type the value the way the device reports it. Capitalization does not matter here, so on also matches a device reporting ON — but text and numbers are not interchangeable, so 1 would not match. See Confirming Commands.

Click Save.

3. Create the Turn OFF command

Repeat the steps above with three changes:

  • Command nameTurn OFF

  • Payload — the same three bytes with the state byte set to 0x00

  • Expected valueoff

Everything else stays the same.

4. Run them and check the result

Go to the States tab, find Turn ON in the Available commands list, and click Execute.

Watch the entry appear in Recent executions:

  1. It starts as Pending while the downlink is on its way.

  2. When the socket's next message arrives reporting socket_status: on, the execution turns Confirmed — the platform has seen the device in the state you asked for.

Run Turn OFF and the same thing happens in reverse.

If the execution never confirms

An execution that stays unconfirmed until its window closes is marked Soft warning — delivered, but not confirmed. Work through these in order:

  1. Check the value. Open the Metrics tab and read what socket_status reports now. If the socket switched but reports 1 rather than on, the expected value has to match that form — and a typed literal is always text, so use a {{ parameterName }} reference to a Boolean or Integer parameter instead.

  2. Check the metric. Make sure the Metric you selected is the one fed by socket_status, and that it is mapped and receiving readings.

  3. Check the window. The default window is 1.5 × the device's data sending interval. If that interval is not set on the device, set it — see Convergence timeout.

  4. Check the payload. Run Try Encoder again and compare the bytes against the manufacturer's documentation.

Next

  • Put the two commands on a dashboard with a Control widget so the team can switch the socket without opening the device.

  • Let a rule operate the socket on its own — see Running Device Commands.